In this Article I will cover the simple process of making sure your Virtual environment is protected during power outages & is safely shuts down all the virtual machines and the Host & guest vm's are powered on when power resumes.

Step 1 : Upload Install Files.

Browse local data store and upload the Power chute network shutdown installation files from the cd media / download URL provided by APC.

Step 2 : Open firewall ports

esxcfg-firewall -o 3052,udp,in,apcups
esxcfg-firewall -o 3052,udp,out,apcups
esxcfg-firewall -o 3052,tcp,in,apcups
esxcfg-firewall -o 3052,tcp,out,apcups
esxcfg-firewall -o 6547,tcp,in,apcups
esxcfg-firewall –q

Step 3 : create temp directory

mkdir /tmp/APCUPS

Step 4 : Change to root directory

cd /

Step 5 : Find the location of the Install files i.e. local datastore or SAN Lun location

find –name jre*

Note: You need to do this only if you are unaware of the path. I genrally run the above command and copy and paste the path in my next step to avoid mistakes.

Step 6 : copy the install files to the temp directory

cp /vmfs/volumes/4c20e143-b448c7f0-e90b-d8d385be3d78/APCUPS/*.* /tmp/APCUPS/

Step 7 : change directory to install directory

cd /tmp/APCUPS/


Step 8 : Change permissions on the installation files
so install can be performed by root

chmod 777

Step 9 : Start the installation


default group 1
default directory
install java bundle enter

Step 10 : Change Directory to installed area

cd /opt/APC/PowerChute/group1/

Step 11 : Start the configuration wizard


start the service once the wizard is complete

If service fails to start automatically you run the following commands manually OR simply restart the ESX host.

/etc/rc.d/init.d/PowerChute stop
etc/rc.d/init.d/PowerChute start

Now you need to configure your shutdown options according to your requirements by connecting to your host on port 6547. In my case the ip address used for the host was

That's all your UPS configuration up and running within minutes. :)